Owners of major assets with
cooling tower equipment are usually faced with conflicting demands that
are seeking high performance at lowest cost.
Aquarius has placed particular emphasis on developing equipment that addresses those needs
Click a heading below for more information.
The KPI 3 is our third
generation of “Best Practice” controllers for cooling
systems. They monitor, control and data log – pH, ORP,
Conductivity, Temperature, and with Linear Polarization corrosion rates
for both umpy and pit rate on two separate metals, typically mild steel
and copper.
Corrosion probes are ring specimens machined from heat exchanger tube
to ensure the same metallurgy and with automatic control on flow
velocity to ensure a very high degree of accuracy.
Combination probes – pH/ORP/GND Ref and Flow/Temp/Conductivity
probes allow for a compact sensor manifold and with differential inputs
for maximum accuracy and freedom from interference such as ground loops.
Installation of a GSM modem and the use of AquaGuard 2 software allows for -
- SMS alarms direct to mobile or cell phone
- 24/7 Service capability
- Remote download of data
- Remote change of set point parameters
- Historical Data Base of downloads in Excel
- Data Summary automated in Excel
- Trend Graphs automated in Excel
- Rapid production of trend graphs for reports
The CT and CP series of
controllers are specifically tailored for programmed dosage of 2
different non-oxidizing biocides, dispersant dosage as well as
automatic bleed off and automatic inhibitor dosage, and with internal
data logging.
The units feature Pre Bleed and Bleed Lockout facilities with automatic
overrides to ensure maximum retention of biocide and maximum bacterial
kill on each dose.
Use of the data log data obtained, either locally via a laptop or
remotely via a GSM modem and AquaGuard 2 software, can highlight
maintenance deficiencies detrimental to the water treatment program
such as overflowing cooling towers, blocked bleed solenoids, or failed
solenoid valves, etc.
The use of our design - self priming peristaltic pumps rated to 350
kPa. (50 psi), with Norprene squeeze tube and glass filled
polypropylene casing, and housing a 16 watt motor ensure reliable &
troublefree dosage of all common water treatment chemicals.
Cooling Water Controllers (CO, CH, CL) -
using ORP control and Oxidising Biocides and data logging
Oxidizing biocides are often seen
as the preferred method of bacterial control in cooling systems. With
this sensor controlled dosage, a consistent level of Oxidizing chemical
can be maintained and monitored in the system 24/7.
Our range of cooling tower
conductivity controllers provide this ability with in-built safety
features and benefits to provide accuracy and data logged history,
alarms and analysis of water treatment
performance. These include:
- ORP sensing and control to
inhibit the growth and proliferation of Legion Ella and other micro
organisms by managing the dosage of oxidizing biocides automatically
to a programmed set point. More Info (Technical Article ORP)
- pH sensing and control to
reduce or elevate pH to improve biocide effectiveness, augment
corrosion control and maximize the cycles of concentration to reduce
water consumption.
- Dosage of Chemicals to
protect the system from scale and corrosion with other cleaning agent
such as dispersants in a combined package
- Data Logging for reporting and recording performance of water treatment regime
Advanced dosage control
technology utilizing ORP & pH sensing has been developed by
Aquarius Technologies and incorporates many features to ensure
reliability and effective management and reporting to enhance this
highly effective water treatment method.
For more information contact us at info@aquariustech.com.au